Plan Review Notes For Permit 01090488 |
Permit Number |
01090488 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-02 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE MISSING GROUNDING | | SYSTEM AT DETACHED STRUCTURES PER | | 230-32. FOOTER STEEL FOR NEW STRUCTURES | | AND COLD WATER PIPE. | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|