2001-11-29 00:00:00******************PROVISO***************
  
  
 EXHAUST DUCTS SHALL TERMINATE OUTSIDE
 THE BUILDING AND SHALL BE LOCTED 10 FT.
 FROM ANY ADJACENT BUIDLING, PARKING
 AREA, ADJACENT PROPERTY LINE, WINDOW,
 DOOR, OR AIR INTAKE OPENING AND SHALL
 BE LOCATED AT LEAST 10 FT. ABOVE THE
 ADJOINING GRADE LEVEL.
  
 PLAN SHEET M2.1, NOTE INDICATES SLOPE OF
 GREASE DUCT TO BE 1/8" .SLOPE SHALL
 BE A MINIMUM OF 1" PER FT.
  