2001-10-01 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.FIRE RATED ENCLOSURE SHALL BE 1 HR
 AND SHALL COMPLY WITH 1997 SMC
 505.9.1 THROUGH 505.10.
  
 A. MINIMUM OF 6" SHALL BE MAINTAINED
 BETWEEN THE DUCT & INTERIOR OF
 THE ENCLOSURE.NOTE, DUCT SHALL
 BE LEFT EXPOSED UNTIL INSPECTION
 OF WELDS.
  
 B. THE ENCLOSURE SHALL BE USED
 EXCLUSIVELY TO ENCLOSE A SINGLE
 GREASE EXHAUST SYSTEM. NO OTHER
 SYSTEM SHALL BE ENCLOSED WITH
 GREASE DUCT.
  
 C. ACCESS TO CLEANOUT OPENINGS SHALL
 HAVE THE SAME FIRE RESISTANCE
 RATING AS THE ENCLOSURE.
  
 5.MINIMUM OF 1" PER FOOT SLOPE TOWARD
 HOOD OR AN APPROVED RESIDUE TRAP.
 1997 SMC 505.4.
  
 6.WILL THERE ALSO BE A RETURN AIR
 IN THE KITCHEN AREA?AREAS WITH
 300 CFM OR GREATER REQUIRE A R/A
 FROM THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.