Plan Review Notes For Permit 01090475 |
Permit Number |
01090475 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-01 00:00:00 | ******************DENIED**************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | ASHRAE 62-89. | | | | 2.AIR BALANCE SCHEDULE SHOWING | | COMPLIANCE WITH 1997 SMC 501.2. | | | | 3.FIRE RATED ENCLOSURE SHALL BE 1 HR | | AND SHALL COMPLY WITH 1997 SMC | | 505.9.1 THROUGH 505.10. | | | | A. MINIMUM OF 6" SHALL BE MAINTAINED | | BETWEEN THE DUCT & INTERIOR OF | | THE ENCLOSURE.NOTE, DUCT SHALL | | BE LEFT EXPOSED UNTIL INSPECTION | | OF WELDS. | | | | B. THE ENCLOSURE SHALL BE USED | | EXCLUSIVELY TO ENCLOSE A SINGLE | | GREASE EXHAUST SYSTEM. NO OTHER | | SYSTEM SHALL BE ENCLOSED WITH | | GREASE DUCT. | | | | C. ACCESS TO CLEANOUT OPENINGS SHALL | | HAVE THE SAME FIRE RESISTANCE | | RATING AS THE ENCLOSURE. | | | | 5.MINIMUM OF 1" PER FOOT SLOPE TOWARD | | HOOD OR AN APPROVED RESIDUE TRAP. | | 1997 SMC 505.4. | | | | 6.WILL THERE ALSO BE A RETURN AIR | | IN THE KITCHEN AREA?AREAS WITH | | 300 CFM OR GREATER REQUIRE A R/A | | FROM THAT SPACE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|