Plan Review Notes For Permit 01090475
Permit Number 01090475
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-09-18 00:00:001) EXHAUST/FRESH AIR DUCT SHAFT SHOWN
 ON PAGE A-1. PLEASE BE ADVISED THAT
 IN BUILDINGS TWO OR MORE STORIES, GREASE
 DUCT ENCLOSURES SHALL BE USED FOR NO
 OTHER PURPOSE. SEE 1997 MECHANICAL CODE
 505.9.2.
 2) ENCLOSURE AROUND GREASE DUCT SHALL
 BE AT LEAST ONE HOUR RATED.
 3) EXHAUST DUCT MINIMUM OF 1/8" SLOPE
 PER FOOT SHOWN ON M2.1 MINIMUM SLOPE
 SHALL NOT BE LESS THAN 1" PER FOOT SLOPE
 SEE 1997 MECHANICAL CODE.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT AND SUPPRESSION SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910