Plan Review Notes For Permit 01090475 |
Permit Number |
01090475 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-09-18 00:00:00 | 1) EXHAUST/FRESH AIR DUCT SHAFT SHOWN | | ON PAGE A-1. PLEASE BE ADVISED THAT | | IN BUILDINGS TWO OR MORE STORIES, GREASE | | DUCT ENCLOSURES SHALL BE USED FOR NO | | OTHER PURPOSE. SEE 1997 MECHANICAL CODE | | 505.9.2. | | 2) ENCLOSURE AROUND GREASE DUCT SHALL | | BE AT LEAST ONE HOUR RATED. | | 3) EXHAUST DUCT MINIMUM OF 1/8" SLOPE | | PER FOOT SHOWN ON M2.1 MINIMUM SLOPE | | SHALL NOT BE LESS THAN 1" PER FOOT SLOPE | | SEE 1997 MECHANICAL CODE. | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | FOR HOOD,DUCT AND SUPPRESSION SYSTEM. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|