Plan Review Notes
Plan Review Notes For Permit 01090475
Permit Number 01090475
Review Stop B
Sequence Number 1
Notes
Date Text
2001-09-28 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090475
 700 S DIXIE HWY
 CONT: THE WEITZ CO
 TEL: (561) 686-5511
  
 1)- THE PLANS DO NOT INDICATE IF THIS IS
 A ACCESORY OCCUPANCY, A FLOOR PLAN OF
 THE FIRST FLOOR WILL INDICATE THE USEAGE
 OR MAIN OCCUPANCY WILL BE.
  
 2)- SBC1203.4.1. THIS SECTION DEALS WITH
 TOILET ROOMS OPENING DIRECTLY INTO THE
 ROOM USED FOR PREPARATION OF FOOD, AGAIN
 THIS PLAN DOESN'T INDICATE WHERE THE FAC
 ILITIES ARE?
  
 3)- SBC TABLE 803.3 MISSING ARE THE
 MINIMUM INTERIOR FINISH CLASSIFICATION.
  
 4)- THERE IS A DOOR ON THE LEFT SIDE OF
 THE PLAN DOES THIS GO TO THE EXTERIOR?
 IF SO SHOW COMPLIANCE WITH 1205.1.2.3/
 1205.1.2.4.
  
 THE PLANS INDICATE THAT A FIRE RATED
 CHASE WILL EXTEND THROUGH TO THE ROOF,
 (M2.1) SBC 705.2.3.1 SHOW UL LISTING
 AND THE TERMINATION DESIGNS.