2001-09-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090332
 1601 BELVEDERE RD./ #211
 SERVICO CENTRE ASSOCIATES, LTD.
 TEL: (561) 394-5200
 FAX: (561) 394-5498
  
 SBC= 1997 STANDARD BUILDING CODE
 "PLAN REVIEW"
 1)- SHEET #1 INDICATES THAT WOOD BUCKS
 WILL BE USED, SBC 604/ 609.2.1 TYPE I&
 TYPE II BUILDINGS REQUIRE NON-COMBUST-
 IBLE MATERIALS IN WALLS, BACKING, BUCKS
 ARE INCLUDED, FIRE RESISTANT TREATED
 WOOD IS ACCEPTED.
  
 2)- SHEET #3 GENERAL NOTES, NOTE #1,
 THIS BUILDING IS A TYPE I /OR TYPE II
 BUILDING APPROX. 16 STORIES HIGH.
  
 3)- SBC 1004.1.4. ARRANGEMENTS & NUMBER
 OF EXITS. WHERE 2 OR MORE EXITS OR EXIT
 ACCESS DOORS ARE REQUIRED, AT LEAST 2 OF
 THE EXIT DOORS SHALL BE PLACED A DIS-
 TAANCE APART EQUAL TO NOT LESS THAN ONE
 HALF THE LENGTH OF THE MAXIMUM DIAGONAL
 DIMENSION OF THE BUILDING OR AREA.
  
 4)_SBC TABLE 803.3 MISSING INFORMATION
 FOR MINIMUM INTERIOR FINISH CLASSIFICA-
 TION.
  
 5)- TYPE I TYPE II BUILDINGS ARE
 REQUIRED TO HAVE FIRE SPRINKLERS, PLANS
 FOR FIRE SPRINKLERS THERE LAYOUT ALL
 DEVICESTO BE INCLUDED BEFORE A BUILD-
 ING PERMIT CAN BE ISSUED.
  
 6)- FL ACCESSIBILITY CODE4.1.6.2.2.
 ALTERATIONA MADE TO PROVIDE AN ACCESS-
 IBLE PATH OF TRAVEL TO ALTERED AREAS
 SHALL BE DEEEMED DISPROPORTIONATE TO THE
 OVERALL ALTERATION WHEN THE COST EXCEEDS
 20 % OF THE CODT OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA.
  
 THE CONTRACTOR TO SHOW WHERE $4,000 WILL
 BE USED UP DATING THE AREA TO THE FL
 ACCESSIBILITY CODE, SHEET 3 NOTE 21 WILL
 QUALIFY AS PART OF THESE MONIES REQUIRED
 TO BE ALLOCATED.
 THE CONFRENCE ROOM DOOR DOESN'T MEET THE
 MANEUVERING CLEARENCES 4.13.6.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412