Date |
Text |
2001-09-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01090332 |
| 1601 BELVEDERE RD./ #211 |
| SERVICO CENTRE ASSOCIATES, LTD. |
| TEL: (561) 394-5200 |
| FAX: (561) 394-5498 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| "PLAN REVIEW" |
| 1)- SHEET #1 INDICATES THAT WOOD BUCKS |
| WILL BE USED, SBC 604/ 609.2.1 TYPE I& |
| TYPE II BUILDINGS REQUIRE NON-COMBUST- |
| IBLE MATERIALS IN WALLS, BACKING, BUCKS |
| ARE INCLUDED, FIRE RESISTANT TREATED |
| WOOD IS ACCEPTED. |
| |
| 2)- SHEET #3 GENERAL NOTES, NOTE #1, |
| THIS BUILDING IS A TYPE I /OR TYPE II |
| BUILDING APPROX. 16 STORIES HIGH. |
| |
| 3)- SBC 1004.1.4. ARRANGEMENTS & NUMBER |
| OF EXITS. WHERE 2 OR MORE EXITS OR EXIT |
| ACCESS DOORS ARE REQUIRED, AT LEAST 2 OF |
| THE EXIT DOORS SHALL BE PLACED A DIS- |
| TAANCE APART EQUAL TO NOT LESS THAN ONE |
| HALF THE LENGTH OF THE MAXIMUM DIAGONAL |
| DIMENSION OF THE BUILDING OR AREA. |
| |
| 4)_SBC TABLE 803.3 MISSING INFORMATION |
| FOR MINIMUM INTERIOR FINISH CLASSIFICA- |
| TION. |
| |
| 5)- TYPE I TYPE II BUILDINGS ARE |
| REQUIRED TO HAVE FIRE SPRINKLERS, PLANS |
| FOR FIRE SPRINKLERS THERE LAYOUT ALL |
| DEVICESTO BE INCLUDED BEFORE A BUILD- |
| ING PERMIT CAN BE ISSUED. |
| |
| 6)- FL ACCESSIBILITY CODE4.1.6.2.2. |
| ALTERATIONA MADE TO PROVIDE AN ACCESS- |
| IBLE PATH OF TRAVEL TO ALTERED AREAS |
| SHALL BE DEEEMED DISPROPORTIONATE TO THE |
| OVERALL ALTERATION WHEN THE COST EXCEEDS |
| 20 % OF THE CODT OF THE ALTERATION TO |
| THE PRIMARY FUNCTION AREA. |
| |
| THE CONTRACTOR TO SHOW WHERE $4,000 WILL |
| BE USED UP DATING THE AREA TO THE FL |
| ACCESSIBILITY CODE, SHEET 3 NOTE 21 WILL |
| QUALIFY AS PART OF THESE MONIES REQUIRED |
| TO BE ALLOCATED. |
| THE CONFRENCE ROOM DOOR DOESN'T MEET THE |
| MANEUVERING CLEARENCES 4.13.6. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 X 8412 |