2001-09-13 00:00:00DENIED
 REFERENCE: UNIFORM COUNTYWIDE SWIMMING
 POOL AND SPA CODE.
 1) ALL SUCTION LINES SHALL BE VALVED.
 SECTION 39
 2) POOL HEATER NOT SHOWN ON PIPING
 SCHEMATIC. PLEASE SHOW HOW IT WILL BE
 PIPED AT EQUIPMENT PAD.
 3) POOL LAYOUT PAGE, PLEASE SHOW PIPING
 FOR SHEAR DESCENT WATERFALL AND INDIC-
 ATE PIPE SIZE.
 4) SHOW PIPING TO 3RD INLET. NONE SHOWN.
 5) PAGE 4 OF SHEAR DESCENT WATERFALL
 INSTALLATION INSTRUCTIONS, REQUIRES
 A SEPARATE PUMP. PLEASE SHOW A DETAIL
 OF THAT PUMP AND THE VALVES INDICATED
 FOR THIS SYSTEM.
  