Plan Review Notes For Permit 01090318 |
Permit Number |
01090318 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-09-13 00:00:00 | DENIED | | REFERENCE: UNIFORM COUNTYWIDE SWIMMING | | POOL AND SPA CODE. | | 1) NO SKIMMER OR PIPING SHOWN ON POOL | | LAYOUT DRAWING PAGE. SECTION 37 | | 2) PLEASE SHOW ALL PIPING ON POOL LAYOUT | | PAGE. THERE IS NO PIPING FOR JETS AT | | LOVE BENCH. PLEASE INDICATE IF THESE | | JETS WILL COME OFF RETURN LINES OR WILL | | THEY BE PIPED SEPARATE? | | 3) ALL SUCTION LINES SHALL HAVE A VALVE. | | SECTION 39 | | 4) POOL HEATER NOT SHOWN ON PIPING | | SCHEMATIC. PLEASE SHOW HOW IT WILL BE | | PIPED AT POOL EQUIPMENT PAD. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|