2001-09-13 00:00:00DENIED
 REFERENCE: UNIFORM COUNTYWIDE SWIMMING
 POOL AND SPA CODE.
 1) NO SKIMMER OR PIPING SHOWN ON POOL
 LAYOUT DRAWING PAGE. SECTION 37
 2) PLEASE SHOW ALL PIPING ON POOL LAYOUT
 PAGE. THERE IS NO PIPING FOR JETS AT
 LOVE BENCH. PLEASE INDICATE IF THESE
 JETS WILL COME OFF RETURN LINES OR WILL
 THEY BE PIPED SEPARATE?
 3) ALL SUCTION LINES SHALL HAVE A VALVE.
 SECTION 39
 4) POOL HEATER NOT SHOWN ON PIPING
 SCHEMATIC. PLEASE SHOW HOW IT WILL BE
 PIPED AT POOL EQUIPMENT PAD.
  