2001-11-14 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEERED TRUSSES ARE DESIGNED USING
 DIFFERENT MEAN ROOF HEIGHTS. THERE
 IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. REVIEW ALL ENGINEERED
 TRUSSES AND REVISE AS REQUIRED.
 TABLE 1606.2A SBC 1997.
 2-SOME TRUSSES ARE DESIGNED USING "WALL
 HEIGHT" INSTEAD OF MEAN ROOF HEIGHT.
 WALL HEIGHT APPLIES ONLY TO FLAT ROOF
 SYSTEMS. MEAN ROOF HEIGHT IS USED FOR
 SLOPED ROOF. REVISE AS REQUIRED.
  
 NOTES:
 -THESE COMMENTS HAVE BEING ADDRESED ON
 PREVIOUS REVIEWS.
 -DRAWINGS TO BE FILED UNDER PERMIT #
 01090278.
 -THESE COMMENTS APPLY TO PERMIT #S:
 01090278, 01090280, 01090282, 01090284
 AND 01090288.