2001-10-05 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) THE DESIGN CERTIFICATION FORM MUST |
| HAVE THE WET SIGNATURE OF THE DESIGN |
| PROFESSIONAL IN ADDITION TO THE DATE AND |
| HIS EMBOSSED SEAL. |
| |
| 4) SHEET T-1 INDICATES R-19 ATTIC |
| INSULATION AND THE ENERGY CALCS LIST |
| ATTIC INSULATION WITH R-30. PLEASE |
| CORRECT. |
| |
| 5) SAFETY GLAZING IS REQUIRED IN THE |
| FIXED GLASS WINDOWS AT THE DINING ROOM. |
| 97 SBC SECT. 2405.2.1 |
| |
| 6) SHEET A-3 INDICATES A 5 1/2" RECESS |
| AT BAR AREA, RECESS IS ACTUALLY 12". |
| DETAIL SF6X6 ON SHEET A-4.1 SHOWS (2) |
| 6" STEPS WITH A 10" TREAD, HOWEVER TREAD |
| WIDTH IS LISTED AS 12" AT THE RIGHT OF |
| THE DRAWING. PLEASE CORRECT. NOTE: THE |
| SUM OF TWO RISERS AND A TREAD CAN NOT BE |
| LESS THAN 24" NOR MORE THAN 25". 97 SBC |
| SECT. 1007.3 |
| |
| 7) THERE IS NO DETAIL GIVEN IN THE |
| COLUMN SCHEDULE FOR TAG MC2044A. PLEASE |
| CORRECT. |
| |
| 8) MF811.5 ON SHEET A-3 AND TF811.5 ON |
| SHEET A-4.1 APPEAR TO CORRESPOND WITH |
| EACH OTHER BUT ARE MISLABELED. PLEASE |
| CORRECT. |
| |
| 9) THE (2) TAGS MC1616B ON A-3 APPEARS |
| TO BE INCORRECT. SHOULD BE MC816B. |
| |
| 10) DETAIL 18 ON A-6.1 INDICATES A BEAM |
| HANGER FOR THE GIRDER TRUSS AT THE |
| COVERED PATIO, HOWEVER A TA-6 TRUSS |
| ANCHOR TAG IS ALSO INDICATED ON A-5. |
| PLEASE CLARIFY. |
| |
| 11) PROVIDE ADDITIONAL INFORMATION FOR |
| GIRDER HANGER INDICATED IN DETAIL 18 ON |
| A-6.1. INDICATE THE SPECIFIC HANGER IF |
| FROM A MANUFACTURER OR PROVIDE SPECIFIC |
| DIMENSIONS, SIZE AND SPACING OF BOLT |
| HOLES, TYPE OF WELDS, ETC. |
| |
| 12) ON SHEET A-5 THERE ARE (2) CROSS |
| SECTION TAGS LABELED 18 ON A-6.1 AND |
| THERE ARE NO SECTIONS SHOWN ON A-6.1. |
| |
| 13) THE SECTION TAG LABELED B/B-2.3 ON |
| SHEET A-5 SHOULD REFER TO SHEET A-2.3 |
| AND NOT B-2.3. |
| |
| 14) DETAIL 20 ON A-6.1 DOES NOT CONTAIN |
| ENOUGH INFORMATION. INDICATE SPECIFIC |
| ANCHOR IF FROM A MANUFACTURER OR |
| COMPLETE DETAILED DRAWING IF IT IS TO BE |
| FABRICATED. |
| |
| 15) THE SOIL TEST REPORT CALLS FOR THE |
| EXTERIOR FOUNDATION TO BEAR AT LEAST 18" |
| BELOW FINAL GRADE. THE 18" FOOTING |
| DESIGNATED ON THE PLANS CAN NOT |
| ACCOMPLISH THIS AND MAINTAIN THE MINIMUM |
| 4" ABOVE FINAL GRADE REQUIRED FOR FLOOR |
| ELEVATION BY CITY AMENDMENTS. |
| A FOUNDATION WIDTH OF AT LEAST 18" IS |
| ALSO REQUIRED BY THE SOIL REPORT, THE |
| PLANS INDICATE 16". |
| |
| 16) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - THE APPROVED DRAWINGS FOR THE GLAZED |
| DOUBLE STEEL DOORS |
| |
| 17) THE SITE SPECIFIC ENGINEERING FOR |
| THE NORANDEX PRODUCTS MUST BE SIGNED |
| SEALED AND DATED BY THE DESIGN |
| PROFESSIONAL OF RECORD OF THE STRUCTURE. |
| THE ARCHITECT THAT SIGNED AND SEALED THE |
| PLANS IS NOT THE SAME PERSON THAT SIGNED |
| AND NEGLECTED TO SEAL THE SUBMITTAL. |
| |
| 18)PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 19)PROVIDE ENGINEERING FOR BUTT GLASS |
| ASSEMBLIES PER 1997 SBC 2406.2. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |