Plan Review Notes
Plan Review Notes For Permit 01090167
Permit Number 01090167
Review Stop R
Sequence Number 1
Notes
Date Text
2001-10-05 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE DESIGN CERTIFICATION FORM MUST
 HAVE THE WET SIGNATURE OF THE DESIGN
 PROFESSIONAL IN ADDITION TO THE DATE AND
 HIS EMBOSSED SEAL.
  
 4) SHEET T-1 INDICATES R-19 ATTIC
 INSULATION AND THE ENERGY CALCS LIST
 ATTIC INSULATION WITH R-30. PLEASE
 CORRECT.
  
 5) SAFETY GLAZING IS REQUIRED IN THE
 FIXED GLASS WINDOWS AT THE DINING ROOM.
 97 SBC SECT. 2405.2.1
  
 6) SHEET A-3 INDICATES A 5 1/2" RECESS
 AT BAR AREA, RECESS IS ACTUALLY 12".
 DETAIL SF6X6 ON SHEET A-4.1 SHOWS (2)
 6" STEPS WITH A 10" TREAD, HOWEVER TREAD
 WIDTH IS LISTED AS 12" AT THE RIGHT OF
 THE DRAWING. PLEASE CORRECT. NOTE: THE
 SUM OF TWO RISERS AND A TREAD CAN NOT BE
 LESS THAN 24" NOR MORE THAN 25". 97 SBC
 SECT. 1007.3
  
 7) THERE IS NO DETAIL GIVEN IN THE
 COLUMN SCHEDULE FOR TAG MC2044A. PLEASE
 CORRECT.
  
 8) MF811.5 ON SHEET A-3 AND TF811.5 ON
 SHEET A-4.1 APPEAR TO CORRESPOND WITH
 EACH OTHER BUT ARE MISLABELED. PLEASE
 CORRECT.
  
 9) THE (2) TAGS MC1616B ON A-3 APPEARS
 TO BE INCORRECT. SHOULD BE MC816B.
  
 10) DETAIL 18 ON A-6.1 INDICATES A BEAM
 HANGER FOR THE GIRDER TRUSS AT THE
 COVERED PATIO, HOWEVER A TA-6 TRUSS
 ANCHOR TAG IS ALSO INDICATED ON A-5.
 PLEASE CLARIFY.
  
 11) PROVIDE ADDITIONAL INFORMATION FOR
 GIRDER HANGER INDICATED IN DETAIL 18 ON
 A-6.1. INDICATE THE SPECIFIC HANGER IF
 FROM A MANUFACTURER OR PROVIDE SPECIFIC
 DIMENSIONS, SIZE AND SPACING OF BOLT
 HOLES, TYPE OF WELDS, ETC.
  
 12) ON SHEET A-5 THERE ARE (2) CROSS
 SECTION TAGS LABELED 18 ON A-6.1 AND
 THERE ARE NO SECTIONS SHOWN ON A-6.1.
  
 13) THE SECTION TAG LABELED B/B-2.3 ON
 SHEET A-5 SHOULD REFER TO SHEET A-2.3
 AND NOT B-2.3.
  
 14) DETAIL 20 ON A-6.1 DOES NOT CONTAIN
 ENOUGH INFORMATION. INDICATE SPECIFIC
 ANCHOR IF FROM A MANUFACTURER OR
 COMPLETE DETAILED DRAWING IF IT IS TO BE
 FABRICATED.
  
 15) THE SOIL TEST REPORT CALLS FOR THE
 EXTERIOR FOUNDATION TO BEAR AT LEAST 18"
 BELOW FINAL GRADE. THE 18" FOOTING
 DESIGNATED ON THE PLANS CAN NOT
 ACCOMPLISH THIS AND MAINTAIN THE MINIMUM
 4" ABOVE FINAL GRADE REQUIRED FOR FLOOR
 ELEVATION BY CITY AMENDMENTS.
 A FOUNDATION WIDTH OF AT LEAST 18" IS
 ALSO REQUIRED BY THE SOIL REPORT, THE
 PLANS INDICATE 16".
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - THE APPROVED DRAWINGS FOR THE GLAZED
 DOUBLE STEEL DOORS
  
 17) THE SITE SPECIFIC ENGINEERING FOR
 THE NORANDEX PRODUCTS MUST BE SIGNED
 SEALED AND DATED BY THE DESIGN
 PROFESSIONAL OF RECORD OF THE STRUCTURE.
 THE ARCHITECT THAT SIGNED AND SEALED THE
 PLANS IS NOT THE SAME PERSON THAT SIGNED
 AND NEGLECTED TO SEAL THE SUBMITTAL.
  
 18)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 19)PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202