Plan Review Notes
Plan Review Notes For Permit 01090145
Permit Number 01090145
Review Stop M
Sequence Number 1
Notes
Date Text
2001-09-27 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.EXPLAIN HOW FRESH AIR IS BEING
 INTRODUCED TO SYSTEM.PLAN
 INDICATES OUTSIDE AIR SUPPLIED TO
 SUPPLY/STORAGE ROOM.PLEASE NOTE
 AIR SHALL BE DUCTED INTO AHU NOT
 A "FREE" RETURN INTO A STORAGE/
 SUPPLY ROOM.
  
 3.PROVIDE MAKE, MODEL, BTU OF EXISTING
 EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.