Plan Review Notes For Permit 01090145 |
Permit Number |
01090145 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-09-27 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION FOR REVIEW. | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | ASHRAE 62-89. | | | | 2.EXPLAIN HOW FRESH AIR IS BEING | | INTRODUCED TO SYSTEM.PLAN | | INDICATES OUTSIDE AIR SUPPLIED TO | | SUPPLY/STORAGE ROOM.PLEASE NOTE | | AIR SHALL BE DUCTED INTO AHU NOT | | A "FREE" RETURN INTO A STORAGE/ | | SUPPLY ROOM. | | | | 3.PROVIDE MAKE, MODEL, BTU OF EXISTING | | EQUIPMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | 8388. |
|