2001-09-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090145
 700 S DIXIE / 205-208
 GEORGE A RAY JR
 (561) 714-3740
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- EGRESS REQUIREMENTS FAIL TO MEET
 SINGLE EGRESS REQUIREMENTS
 1020.(2) OVER 3500 SQ FT
 1020. (4) OVER THE 75' LIMIT COMMON PATH
  
 1004.1.3 COMMON PATH OF TRAVEL SHALL NOT
 EXCEED 75'.
  
 1004.1.4. WHERE 2 OR MORE EXITS OR EXIT
 ACCESS DOORS ARE REQUIRED, AT LEAST 2
 OF THE EXIT DOORS SHALL BE PLACED A DIS-
 TANCE APART EQUAL TO NOT LESS THAN ONE
 HALF OF THE LENGTH OF THE MAXIMUM OVER-
 ALL DIAGONAL DIMENSION OF THE BUILDING
 OR AREA.
  
 2)- SBC TABLE 803.3 MISSING IS THE
 MINIMUM FINISH CLASSIFCATION SCHEDULE.
  
 3)- PLANS INDICATE THE BUILDING IS SPRIN
 KLERED, SPRINKLE PLANS WILL BE REQUIRED
 BEFORE THE ISSUANCE OF THE BUILDING
 PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412