Plan Review Notes For Permit 01090145 |
Permit Number |
01090145 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-09-18 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01090145 | | 700 S DIXIE / 205-208 | | GEORGE A RAY JR | | (561) 714-3740 | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1)- EGRESS REQUIREMENTS FAIL TO MEET | | SINGLE EGRESS REQUIREMENTS | | 1020.(2) OVER 3500 SQ FT | | 1020. (4) OVER THE 75' LIMIT COMMON PATH | | | | 1004.1.3 COMMON PATH OF TRAVEL SHALL NOT | | EXCEED 75'. | | | | 1004.1.4. WHERE 2 OR MORE EXITS OR EXIT | | ACCESS DOORS ARE REQUIRED, AT LEAST 2 | | OF THE EXIT DOORS SHALL BE PLACED A DIS- | | TANCE APART EQUAL TO NOT LESS THAN ONE | | HALF OF THE LENGTH OF THE MAXIMUM OVER- | | ALL DIAGONAL DIMENSION OF THE BUILDING | | OR AREA. | | | | 2)- SBC TABLE 803.3 MISSING IS THE | | MINIMUM FINISH CLASSIFCATION SCHEDULE. | | | | 3)- PLANS INDICATE THE BUILDING IS SPRIN | | KLERED, SPRINKLE PLANS WILL BE REQUIRED | | BEFORE THE ISSUANCE OF THE BUILDING | | PERMIT. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|