2001-12-27 00:00:00REVISIONS (A-5 & A-6) AND TRUSSES
 DENIED
  
 1) DETAIL 9 ON A-5 STATES (2) 5/8" DIA.
 THRU- BOLTS EACH GIRDER AND INDICATES
 (2) TWO MEMBER GIRDER TRUSSES JOINED IN
 THE STEEL COLUMN SEAT. GIRDER SG-1 IS
 (1) TWO MEMBER GIRDER TRUSS WITH THE
 STEEL COLUMN SEAT LOCATED AT AN
 INTERMEADIATE POINT OF ITS SPAN.
 THEREFORE, THE 4 THRU-BOLTS INDICATED
 WILL BE LOCATED IN THE 2X6 WEB OF THE
 GIRDER TRUSSES. PLEASE REVIEW THE
 SPECIFIED BOLT SPACING OF THE STEEL
 COLUMN SEAT AND REVISE IF REQUIRED.
  
 2) THERE ARE NO CONNECTORS INDICATED ON
 SHEET A-6 FOR THE HJ7C OR HJ7 TRUSSES.
 PLEASE CORRECT.
  
 3) THE UPLIFT FOR TRUSS H1 (1608#)
 EXCEEDS THE CAPACITY OF THE (2) TC-3S
 (721# EA.) SPECIFIED.
  
 4) TRUSSES H2,H5,AND T1 EXCEED UPLIFT
 CAPACITIES OF SPECIFIED CONNECTORS.
  
 5) TRUSS CJ6A (UPLIFT 468#) EXCEEDS THE
 CAPACITY OF THE SPECIFIED TC1 CONNECTOR
 (417#).
  
 6) TRUSS M3 (UPLIFT 504#) EXCEEDS THE
 CAPACITY OF TC-1 (417#).
  
 7) TRUSS M3A (UPLIFT 1503#) EXCEEDS THE
 CAPACITY OF TC-8 (1410#).
  
 8) TRUSS GR1 (UPLIFT 977# @ JOINT 12)
 EXCEEDS THE CAPACITY OF TC-3 (721#).
  
 9) TRUSS S4 (UPLIFT 1500#) EXCEEDS THE
 CAPACITY OF TC-8 (1410#).
  
 10) TRUSS S8 (UPLIFT 784#) EXCEEDS THE
 CAPACITY OF TC-3 (721#).
  
 11) THERE IS NO TRUSS CONNECTOR GIVEN
 ON REVISED SHEET A-6 FOR TRUSS GR6 WITH
 UPLIFT 971# @ JOINT 14.
  
 THE UPLIFT CAPACITIES OF THE CONNECTORS
 MUST MEET OR EXCEED THE CALCULATED
 UPLIFTS OF THE TRUSSES. PLEASE REVIEW
 AND CORRECT ALL ITEMS LISTED.
 PLEASE CALL IF YOU HAVE ANY QUESTIONS.
  