2001-12-27 00:00:00 | REVISIONS (A-5 & A-6) AND TRUSSES |
| DENIED |
| |
| 1) DETAIL 9 ON A-5 STATES (2) 5/8" DIA. |
| THRU- BOLTS EACH GIRDER AND INDICATES |
| (2) TWO MEMBER GIRDER TRUSSES JOINED IN |
| THE STEEL COLUMN SEAT. GIRDER SG-1 IS |
| (1) TWO MEMBER GIRDER TRUSS WITH THE |
| STEEL COLUMN SEAT LOCATED AT AN |
| INTERMEADIATE POINT OF ITS SPAN. |
| THEREFORE, THE 4 THRU-BOLTS INDICATED |
| WILL BE LOCATED IN THE 2X6 WEB OF THE |
| GIRDER TRUSSES. PLEASE REVIEW THE |
| SPECIFIED BOLT SPACING OF THE STEEL |
| COLUMN SEAT AND REVISE IF REQUIRED. |
| |
| 2) THERE ARE NO CONNECTORS INDICATED ON |
| SHEET A-6 FOR THE HJ7C OR HJ7 TRUSSES. |
| PLEASE CORRECT. |
| |
| 3) THE UPLIFT FOR TRUSS H1 (1608#) |
| EXCEEDS THE CAPACITY OF THE (2) TC-3S |
| (721# EA.) SPECIFIED. |
| |
| 4) TRUSSES H2,H5,AND T1 EXCEED UPLIFT |
| CAPACITIES OF SPECIFIED CONNECTORS. |
| |
| 5) TRUSS CJ6A (UPLIFT 468#) EXCEEDS THE |
| CAPACITY OF THE SPECIFIED TC1 CONNECTOR |
| (417#). |
| |
| 6) TRUSS M3 (UPLIFT 504#) EXCEEDS THE |
| CAPACITY OF TC-1 (417#). |
| |
| 7) TRUSS M3A (UPLIFT 1503#) EXCEEDS THE |
| CAPACITY OF TC-8 (1410#). |
| |
| 8) TRUSS GR1 (UPLIFT 977# @ JOINT 12) |
| EXCEEDS THE CAPACITY OF TC-3 (721#). |
| |
| 9) TRUSS S4 (UPLIFT 1500#) EXCEEDS THE |
| CAPACITY OF TC-8 (1410#). |
| |
| 10) TRUSS S8 (UPLIFT 784#) EXCEEDS THE |
| CAPACITY OF TC-3 (721#). |
| |
| 11) THERE IS NO TRUSS CONNECTOR GIVEN |
| ON REVISED SHEET A-6 FOR TRUSS GR6 WITH |
| UPLIFT 971# @ JOINT 14. |
| |
| THE UPLIFT CAPACITIES OF THE CONNECTORS |
| MUST MEET OR EXCEED THE CALCULATED |
| UPLIFTS OF THE TRUSSES. PLEASE REVIEW |
| AND CORRECT ALL ITEMS LISTED. |
| PLEASE CALL IF YOU HAVE ANY QUESTIONS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |