2001-08-31 00:00:00 | CHECKLIST: | | 1-PROVIDE COMPLETE CALCULATIONS SHOWING | | ALL DESIGN LOADS AND DESIGN CRITERIA | | ASSUMPTIONS. | | -BE SPECIFIC: USE SBC 1997 FOR LOADS | | CONSIDERATIONS. | | 2-THERE IS NO INFORMATION REGARDING THE | | FOOTINGS FOR THE NEW COLUMNS. | | -WHAT ARE THE DESIGN ASSUMPTIONS? SIZE | | OF FOOTINGS? OFF-SET LOADING? | | -ARE EXISTING FOOTINGS ADEQUATE TO | | CARRY THE ADDITIONAL LOAD? SPECIFY | | SIZES. | | 3-HOW MANY STORIES ARE CONSIDERED IN | | THIS BUILDING? |
|