2001-08-28 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW: | | | | 1.MAKE, MODEL AND CFM FOR EXHAUST | | FAN. | | | | 2.INDICATE TERMINATION OF EXHAUST | | FAN.SHALL COMPLY WITH 1997 SMC | | 506.1 AND NFPA 33 5.4. | | | | 3.INDICATE FRESH AIR MAKE UP...NATURAL | | OR MECHANICAL, SHOW COMPLIANCE WITH | | 1997 SMC 501.2.AIR MAKEUP SHALL BE | | LOCATED A MINIMUM OF 10' FROM | | EXHAUST OUTLET. | | | | SPRAY BOOTH CONSTRUSTION SHALL COMPLY | | WITH NFPA 33 CHAPTER 3. | | | | SEPARATE PLANS AND PERMIT REQUIRED FOR | | FIRE SUPRESSION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|