Plan Review Notes
Plan Review Notes For Permit 01081084
Permit Number 01081084
Review Stop R
Sequence Number 1
Notes
Date Text
2001-09-15 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-RECORD NOTICE OF COMMENCEMENT.
 3-NEED TO REVISE ORIGINAL DRAWINGS TO
 REFLECT THE RIGHT DIMENSIONS REQUIRED
 FOR THE PLUMBING FIXTURES. THIS WILL
 HELP EXPEDITE THE REVIEW PROCESS FOR
 FUTURE SUBMITTALS AS WELL.
 4-PROVIDE TWO COPIES OF THE PRELIMINARY
 SUBSURFACE STUDY.
 -ALSO, WILL NEED TO PROVIDE ADDITIONAL
 BORINGS FOR EACH STRUCTURE (BEFORE
 CONSTRUCTION) AS RECOMMENDED IN THE
 PRELIMINARY STUDY.
 5-ENGINEER TO FILL OUT THE DESIGN
 CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. PLEASE, AVOID FUTURE
 DELAYS. THIS FORM IS MISSING IN EVERY
 SUBMITTAL I HAVE REVIEWED.
 6-OWES ADDITIONAL FEES FOR UPDATED
 VALUATION AND RADON FEES. PLEASE, PAY
 ATTACHED RECEIPTS.
 7-CLEARLY INDICATE ON PLANS THE OPTIONS
 SELECTED AND PROVIDE THE CORRESPONDING
 PRODUCT APPROVAL OR CROSS OUT THE
 OPTIONS IF NOT USED.
 8-SEE COMMENTS BY THE PLUMBING PLAN
 EXAMINER AND PROVIDE A/C PLANS FOR
 MECHANICAL PLAN EXAMINER REVIEW.
 9-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
 10-PROVIDE 2 COPIES OF PRODUCT APPROVAL
 FOR WINDOW MULLIONS.
 NOTES:
 -DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT NUMBER 01081084.
 -THESE COMMENTS APPLY TO PERMIT #S:
 01081084, 01081094, 01081098 AND
 01081088.