2001-10-23 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) FULL SETS OF PLANS REQUIRED. PAGE A-2
 NOT INCLUDED IN RESUBMITED SET, AND DEMO
 PAGES NEED TO BE INSERTED. PLEASE SUBMIT
 FULL SETS FOR REVIEW.
 2) PAGE A-1, RM 111. DOOR OUT OF ROOM
 SO AS NOT TO SWING INTO TURNING RADIUS.
 FACBC-97 4.22.3
 3) PAGE A-1 LUNCH ROOM. CLEAR FLOOR
 SPACE FOR PARALLEL, FIXTURE MUST CENTER
 ON CLEAR FLOOR SPACE. SINK ONLY 18" INTO
 CLEAR FLOOR SPACE. FRONTAL APPROACH IS
 REQUIRED. PLEASE SHOW DETAIL AND SHOW
 COMPLIANCE WITH ALL DETAILS OF SEC 4.24
 4) PLEASE SHOW WATER RISER DIAGRAM AS
 REQUESTED IN PREVIOUS PLAN REVIEW. NOTE
 #7 IN PLUMBING NOTES ON PAGE E-1 CALLS
 FOR AIR CHAMBERS, BUT NOTE BY SANITARY
 RISER CALLS FOR AIR HAMMER ARRESTORS. IF
 WATER HAMMER ARRESTORS ARE USED PLEASE
 NOTE IN NOTE #7 AND SHOW THEM IN WATER
 RISER DIAGRAM. PLACEMENT AND SIZE SHALL
 BE PER MANUFACTURES INSTALLATION INSTRU-
 CTIONS AND WH-PDI 201. PLACEMENT SHALL
 BE CLOSE TO FIXTURE NOT AT TOP OF DROP.
 5) PAGE E-1 NOTE #4. FROM PREVIOUS RE-
 VIEW SHOW CONDENSATE SYSTEM SO PLUMBING
 CONTRACTOR CAN INSTALL. SHOW TERMINATION
 OF CONDENSATE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377