2001-10-23 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FACBC-97 |
| |
| 1) FULL SETS OF PLANS REQUIRED. PAGE A-2 |
| NOT INCLUDED IN RESUBMITED SET, AND DEMO |
| PAGES NEED TO BE INSERTED. PLEASE SUBMIT |
| FULL SETS FOR REVIEW. |
| 2) PAGE A-1, RM 111. DOOR OUT OF ROOM |
| SO AS NOT TO SWING INTO TURNING RADIUS. |
| FACBC-97 4.22.3 |
| 3) PAGE A-1 LUNCH ROOM. CLEAR FLOOR |
| SPACE FOR PARALLEL, FIXTURE MUST CENTER |
| ON CLEAR FLOOR SPACE. SINK ONLY 18" INTO |
| CLEAR FLOOR SPACE. FRONTAL APPROACH IS |
| REQUIRED. PLEASE SHOW DETAIL AND SHOW |
| COMPLIANCE WITH ALL DETAILS OF SEC 4.24 |
| 4) PLEASE SHOW WATER RISER DIAGRAM AS |
| REQUESTED IN PREVIOUS PLAN REVIEW. NOTE |
| #7 IN PLUMBING NOTES ON PAGE E-1 CALLS |
| FOR AIR CHAMBERS, BUT NOTE BY SANITARY |
| RISER CALLS FOR AIR HAMMER ARRESTORS. IF |
| WATER HAMMER ARRESTORS ARE USED PLEASE |
| NOTE IN NOTE #7 AND SHOW THEM IN WATER |
| RISER DIAGRAM. PLACEMENT AND SIZE SHALL |
| BE PER MANUFACTURES INSTALLATION INSTRU- |
| CTIONS AND WH-PDI 201. PLACEMENT SHALL |
| BE CLOSE TO FIXTURE NOT AT TOP OF DROP. |
| 5) PAGE E-1 NOTE #4. FROM PREVIOUS RE- |
| VIEW SHOW CONDENSATE SYSTEM SO PLUMBING |
| CONTRACTOR CAN INSTALL. SHOW TERMINATION |
| OF CONDENSATE. |
| |
| REVIEW BY KEN STEVENS |