Plan Review Notes
Plan Review Notes For Permit 01080991
Permit Number 01080991
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-30 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S ARE TO BE SHOWN ON PLANS AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
  
  
 2)NOTE: PLEASE NOTE, WHAT IS THE SIZE OF
 EXISTING MAIN AND LOAD? PLANS SHOW
 ADDING NEW PANEL "B". PLEASE CLARFIY
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE SHOWN
 FOR PANELS BUT NOT FOR MAINS.
  
 4)NOTE: PLEASE NOTE CLEARENCES ON PLANS
 FOR DISCONNECT SHOWN FOR AHU #2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372