Plan Review Notes For Permit 01080991 |
Permit Number |
01080991 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-30 00:00:00 | ****************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE THAT ALL BRANCH | | CIRCUIT #`S ARE TO BE SHOWN ON PLANS AND | | CORRELATE WITH SUBMITTED PANEL SCHEDULES | | | | | | 2)NOTE: PLEASE NOTE, WHAT IS THE SIZE OF | | EXISTING MAIN AND LOAD? PLANS SHOW | | ADDING NEW PANEL "B". PLEASE CLARFIY | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | PLEASE NOTE THAT AIC RATINGS WERE SHOWN | | FOR PANELS BUT NOT FOR MAINS. | | | | 4)NOTE: PLEASE NOTE CLEARENCES ON PLANS | | FOR DISCONNECT SHOWN FOR AHU #2. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|