2001-08-21 00:00:00 | *************** UNSAT ************ |
| |
| 1)NOTE: PLEASE NOTE THAT PLANS SUBMITTED |
| FOR ELECTRICAL REVIEW WERE NOT CLEAR |
| ENOUGH IN DETAIL FOR PROPER REVIEW. |
| PLEASE SUBMIT PLANS FOR ELECTRICAL |
| LAYOUTS. PLEASE NOTE THAT PLANS NEED TO |
| BE RE-DRAWN UNDER COUNTY-WIDE AND CITY- |
| WIDE ADMINISTRATIVE CODE 104.2.7. |
| |
| PLEASE NOTE THAT THE FOLLOWING ARE SOME |
| ITEMS THAT COULD BE SEEN ON PAGE 1 OF 2 |
| OF THE ELEC SUBMITTED. |
| |
| 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| PLEASE SHOW DOORS TO ALL BEDROOMS. |
| |
| 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210-8-A-6. |
| |
| 4) PLEASE NOTE EITHER MISSING EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210-70 OF THE NEC. |
| PLEASE DRAW IN SWITCH LEGS AND SHOW |
| DEVICES THAT ARE BEING USED. |
| |
| 5)NOTE: PLEASE PROVIDE CLARIFICATION ON |
| PANELS AND IF NEW EQUIPMENT IS BEIING |
| INSTALLED? EXISTING? RE-PULLING |
| CONDUCTORS?? |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |