Plan Review Notes
Plan Review Notes For Permit 01080720
Permit Number 01080720
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-21 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT PLANS SUBMITTED
 FOR ELECTRICAL REVIEW WERE NOT CLEAR
 ENOUGH IN DETAIL FOR PROPER REVIEW.
 PLEASE SUBMIT PLANS FOR ELECTRICAL
 LAYOUTS. PLEASE NOTE THAT PLANS NEED TO
 BE RE-DRAWN UNDER COUNTY-WIDE AND CITY-
 WIDE ADMINISTRATIVE CODE 104.2.7.
  
 PLEASE NOTE THAT THE FOLLOWING ARE SOME
 ITEMS THAT COULD BE SEEN ON PAGE 1 OF 2
 OF THE ELEC SUBMITTED.
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE SHOW DOORS TO ALL BEDROOMS.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE DRAW IN SWITCH LEGS AND SHOW
 DEVICES THAT ARE BEING USED.
  
 5)NOTE: PLEASE PROVIDE CLARIFICATION ON
 PANELS AND IF NEW EQUIPMENT IS BEIING
 INSTALLED? EXISTING? RE-PULLING
 CONDUCTORS??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372