Plan Review Notes
Plan Review Notes For Permit 01080699
Permit Number 01080699
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-16 00:00:001) THE EXISTING UNDERGROUND 500 GALLON
 FUEL TANK IS TO BE REMOVED IN
 ACCORDANCE WITH NFPA 30.
 2) NO CUT SHEETS OR PRODUCT APPROVALS
 PROVIDED FOR NEW ABOVEGROUND FUEL
 TANK. PLEASE PROVIDE PRODUCT APPROVALS
 FOR TANK.
 3) NO INFORMATION PROVIDED REGARDING
 IDENTIFICATION OR WARNING LABELS
 PROVIDED FOR TANK.
 4) PLEASE INDICATE DISTANCES FROM THE
 BUILDING TO THE RELOCATED DAY TANK AND
 THE NEW ABOVEGROUND FUEL TANK.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910