2001-08-16 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES ATTACHED FROM
 PREVIOUS REVIEWS UNDER MASTER PERMITS.
  
 2) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE THAT THERE ARE MANY PLACES
 ON THE PLANS THAT SHOW A "J-BOX". PLEASE
 NOTE THAT THESE LOCATIONS NEED TO SHOW
 A LIGHTING FIXTURE.?
  
 3)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 BEING SUBMITTED SHOWING A NEW SERVICE?
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULES
 APPEAR TO HAVE BEEN MISPRINTED. PLEASE
 NOTE THAT SUB-PANELS "B, C" ARE SHOWN
 AS SINGLE SPACES. PLEASE NOTE THAT
 LIGHTING/BATH/LAUNDRYECT ARE SHOWN
 WITH BREAKERS 60 AND 80AMPS(MISPRINT)??
  
 5)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE NOTE THAT HEATING LOAD IS SHOWN
 AT 235KW.(MISPRINT)??
  
 6)NOTE: PLEASE NOTE PLANS MISSING THE
 REQ`D DISCONNECTS FOR 440-11.PLEASE
 CLARIFY TWO WP GFI RECEPTS SHOWN ?
  
 7)NOTE: PLEASE NOTE UPSTAIRS EGRESS
 LIGHTING REQ`D PER 210-70 (HALLWAY)
  
 8) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING OUTLETS IN SOME LOCATIONS.
  
 9)NOTE: PLEASE NOTE/CLARIFY PIPE SIZE
 TO PANEL "C"?? SHOWN AS 4"? MISPRINT?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  