2001-08-16 00:00:00 | *************** UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE NOTES ATTACHED FROM |
| PREVIOUS REVIEWS UNDER MASTER PERMITS. |
| |
| 2) PLEASE NOTE EITHER MISSING EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210-70 OF THE NEC. |
| PLEASE NOTE THAT THERE ARE MANY PLACES |
| ON THE PLANS THAT SHOW A "J-BOX". PLEASE |
| NOTE THAT THESE LOCATIONS NEED TO SHOW |
| A LIGHTING FIXTURE.? |
| |
| 3)NOTE: PLEASE NOTE THAT PLANS ARE NOW |
| BEING SUBMITTED SHOWING A NEW SERVICE? |
| PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULES |
| APPEAR TO HAVE BEEN MISPRINTED. PLEASE |
| NOTE THAT SUB-PANELS "B, C" ARE SHOWN |
| AS SINGLE SPACES. PLEASE NOTE THAT |
| LIGHTING/BATH/LAUNDRYECT ARE SHOWN |
| WITH BREAKERS 60 AND 80AMPS(MISPRINT)?? |
| |
| 5)NOTE: PLEASE SEE LOAD CALCULATIONS, |
| PLEASE NOTE THAT HEATING LOAD IS SHOWN |
| AT 235KW.(MISPRINT)?? |
| |
| 6)NOTE: PLEASE NOTE PLANS MISSING THE |
| REQ`D DISCONNECTS FOR 440-11.PLEASE |
| CLARIFY TWO WP GFI RECEPTS SHOWN ? |
| |
| 7)NOTE: PLEASE NOTE UPSTAIRS EGRESS |
| LIGHTING REQ`D PER 210-70 (HALLWAY) |
| |
| 8) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING OUTLETS IN SOME LOCATIONS. |
| |
| 9)NOTE: PLEASE NOTE/CLARIFY PIPE SIZE |
| TO PANEL "C"?? SHOWN AS 4"? MISPRINT? |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |