Plan Review Notes For Permit 01080648 |
Permit Number |
01080648 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-21 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | 1.REFRIGERANT DETECTOR SHALL BE TIED | | TO AN AUDIBLE/VISUAL ALARM AND SHALL | | BE LOCATED OUTSIDE THE ENTRANCE OF | | MECHANICAL ROOM AS WELL AS INSIDE | | THE MECHANICAL ROOM. | | 1997 SMC 1105.3. | | | | 2.A SIGN SHALL BE POSTED ON THE | | MACHINERY ROOM DOOR PROHIBITING | | ACCESS OF UNAUTHORIZED PERSONNEL. | | | | 3.INDICATED ON PLAN THE TERMINATION OF | | RELIEF DEVICES - SHALL TERMINATE | | OUTSIDE AT A LOCATION NOT LESS THAN | | 15' ABOVE THE ADJOINING GROUND LEVEL | | AND NOT LESS THAN 20' FROM ANY | | WINDOWM VENTILATION OPENING, OR EXIT | | TO ANY BUILDING. | | | | NOTE:TEST OF DETECTOR, ALARM AND | | MECHANICAL VENTILATING SYSTEM | | SHALL BE PERFORMED AS PER 1997 | | SMC 1105.4 FOR COMPLAINCE WITH | | SECTION 1105 OF THE SMC. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|