Plan Review Notes For Permit 01080613 |
Permit Number |
01080613 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2002-01-08 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE, PLANS STILL NEED TO | | CORRELATE. | | PLEASE NOTE, 300A FUSES ARE SHOWN ON | | RISER AND 350A FUSES SHOWN ON SCHEDULE? | | PLEASE CLARIFY/ | | | | 2)NOTE: PLEASE NOTE THAT NOW A NEW SERVI | | CE IS BEING SUBMITTED FOR REVIEW AND | | THERE ARE NEW COMMENTS. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 4)NOTE: PLEASENOTE LOAD IS SHOWN | | LARGER THAN 300A OCP. | | | | 5)NOTE: PLEASE NOTE LOAD CALCULATIONS | | FOR EACH UNIT IS NOT SHOWN? PLEASE SHOW. | | PLEASE CALL. | | | | 6)NOTE: PLEASE PROVIDE LAYOUT FOR UNITS | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|