2002-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE, PLANS STILL NEED TO
 CORRELATE.
 PLEASE NOTE, 300A FUSES ARE SHOWN ON
 RISER AND 350A FUSES SHOWN ON SCHEDULE?
 PLEASE CLARIFY/
  
 2)NOTE: PLEASE NOTE THAT NOW A NEW SERVI
 CE IS BEING SUBMITTED FOR REVIEW AND
 THERE ARE NEW COMMENTS.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASENOTE LOAD IS SHOWN
 LARGER THAN 300A OCP.
  
 5)NOTE: PLEASE NOTE LOAD CALCULATIONS
 FOR EACH UNIT IS NOT SHOWN? PLEASE SHOW.
 PLEASE CALL.
  
 6)NOTE: PLEASE PROVIDE LAYOUT FOR UNITS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  