Plan Review Notes For Permit 01080613 |
Permit Number |
01080613 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-11-28 00:00:00 | BUILDING PLAN REVIEW | | PERMIT# 01080613 | | 1320 HENRIETTA | | REVISION OCT 2001 | | CONT: COMPLETE PROPERTY MAN. | | TEL: 252-8372 | | | | 1)- STATE REQQUIREMENTS FOR PRE-CONSTRUC | | TION SOIL TREATMENT FOR TTERMITES.STUCCO | | IS TO STOP 6" ABOVE GRADE TO LEAVE AN | | EXTERIOR VERTICAL BARRIER. | | 2)- AT THE ENTRY TO THE LAUNDRY A 8" VER | | TICAL STEP IS SHOWN, FAIR HOUSING ACT | | ANSI A117.1.4.5 GROUND AND FLOOR SURFACE | | TREATMENTS. INCLUDES WALKWAYS FOR ALL | | COMMON ELEMENTS, & RAMPS. | | 3)- SHOW LOCATION OF PROPOSED LAUNDRY | | PLOT PLAN OR SURVEY. | | 4)- SBC1606.2.6.2 PRODUCT APPROVAL FOR | | ENTRY DOOR. | | 5)- SBC 1707.5 CLAY & CEMENT TILE ROOF- | | ING SHALL BE REQUIRE PRODUCT TESTING FOR | | 110 MPH WIND ZONE. SBCCI OR DADE COUNTY. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X8412 |
|