2002-03-06 00:00:00 | *************TRUSSES DENIED************* |
| |
| 1) THE TRUSS DRAWINGS ARE REQUIRED TO |
| HAVE THE EMBOSSED SEAL OF THE TRUSS |
| ENGINEER. |
| |
| 2) PLEASE CORRECT WINDLOAD LISTED ON THE |
| TRUSS LAYOUT TO THE SAME AS THAT LISTED |
| ON THE TRUSS DRAWINGS. |
| |
| 3) THE DESIGNER OF RECORD FOR THE |
| STRUCTURE IS REQUIRED TO STAMP, SIGN AND |
| DATE THE TRUSS LAYOUT. THE STAMP SHOULD |
| STATE THAT THE LAYOUT AND DRAWINGS HAVE |
| BEEN REVIEWED AND APPROVED BY HIM. |
| THIS IS IN ADDITION TO THE LETTER FROM |
| DESIGNER OF RECORD. |
| |
| 4)THE UPLIFT GIVEN ON THE TRUSS DRAWINGS |
| EXCEEDS THE CAPACITIES OF THE CONNECTORS |
| SPECIFIED IN THE SCHEDULE ON SHEET 6 OF |
| THE PLANS FOR SEVERAL OF THE TRUSSES. |
| T-21 @ 15= 1869# > A2 = 1060# |
| T-7 @ 2= 3339# > A5 = 2650# |
| T-8 @ 2= 2167# > A3 = 1300# |
| T-9 @ 2= 2234# > A3 = 1300# |
| T-3 @ 2&6= 1516# > A1 =755# |
| T-32,T-33,T-26,T-27,T-28,ETC. |
| PLEASE REVIEW TRUSS DRAWINGS AND |
| CONNECTOR SCHEDULE AND MAKE CORRECTIONS |
| AS NECESSARY. |
| |
| AN ADDITIONAL RESUB FEE WILL BE ASSESSED |
| FOR SUBSEQUENT RESUBS. THERE WAS NO |
| CHARGE FOR THE FIRST RESUB. SEE ATTACH- |
| MENT. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |