Plan Review Notes
Plan Review Notes For Permit 01080609
Permit Number 01080609
Review Stop R
Sequence Number 6
Notes
Date Text
2002-03-06 00:00:00*************TRUSSES DENIED*************
  
 1) THE TRUSS DRAWINGS ARE REQUIRED TO
 HAVE THE EMBOSSED SEAL OF THE TRUSS
 ENGINEER.
  
 2) PLEASE CORRECT WINDLOAD LISTED ON THE
 TRUSS LAYOUT TO THE SAME AS THAT LISTED
 ON THE TRUSS DRAWINGS.
  
 3) THE DESIGNER OF RECORD FOR THE
 STRUCTURE IS REQUIRED TO STAMP, SIGN AND
 DATE THE TRUSS LAYOUT. THE STAMP SHOULD
 STATE THAT THE LAYOUT AND DRAWINGS HAVE
 BEEN REVIEWED AND APPROVED BY HIM.
 THIS IS IN ADDITION TO THE LETTER FROM
 DESIGNER OF RECORD.
  
 4)THE UPLIFT GIVEN ON THE TRUSS DRAWINGS
 EXCEEDS THE CAPACITIES OF THE CONNECTORS
 SPECIFIED IN THE SCHEDULE ON SHEET 6 OF
 THE PLANS FOR SEVERAL OF THE TRUSSES.
 T-21 @ 15= 1869# > A2 = 1060#
 T-7 @ 2= 3339# > A5 = 2650#
 T-8 @ 2= 2167# > A3 = 1300#
 T-9 @ 2= 2234# > A3 = 1300#
 T-3 @ 2&6= 1516# > A1 =755#
 T-32,T-33,T-26,T-27,T-28,ETC.
 PLEASE REVIEW TRUSS DRAWINGS AND
 CONNECTOR SCHEDULE AND MAKE CORRECTIONS
 AS NECESSARY.
  
 AN ADDITIONAL RESUB FEE WILL BE ASSESSED
 FOR SUBSEQUENT RESUBS. THERE WAS NO
 CHARGE FOR THE FIRST RESUB. SEE ATTACH-
 MENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202