2002-01-09 00:00:00TRUSSES DENIED
  
 1) PROVIDE (2) SETS OF TRUSS DRAWINGS
 AND LAYOUTS. THE LAYOUTS ARE REQUIRED TO
 BE SIGNED, SEALED AND DATED BY THE TRUSS
 ENGINEER. THE ENGINEER'S TITLE BLOCK IS
 REQUIRED. INDICATE THE DESIGN CRITERIA
 USED ON THE LAYOUT. ASCE7-95 (140 MPH
 WINDLOAD) OR 97 SBC SECTION 1606 (110MPH
 WINDLOAD).
  
 2) THE LAYOUT MUST BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR
 THE STRUCTURE (JOHN AVERKAMP, INC.).
 THIS IS TO BE INDICATED ON THE TRUSS
 LAYOUT.
  
 3) THE DESIGN CRITERIA INDICATED ON THE
 TRUSS DRAWINGS IS INCORRECT. THE CORRECT
 DESIGN CRITERIA IS ASCE7-95 (140 MPH
 WINDLOAD) OR 1997 STANDARD BUILDING CODE
 SECTION 1606 (110 MPH WINDLOAD).
  
 4) THE TRUSS DRAWINGS ARE REQUIRED TO BE
 DATED BY THE TRUSS ENGINEER INDICATING
 THE DATE THEY WERE SEALED.
  
 5) THE TRUSS LAYOUT AND THE ROOF FRAMING
 PLAN (SHEET 6) HAVE SIGNIFICANT
 DIFFERENCES. PLEASE SUBMIT A REVISED
 ROOF FRAMING PLAN.
  
 6) TRUSS T1 (UPLIFT 1891#) EXCEEDS THE
 CAPACITY OF THE SPECIFIED CONNECTOR, A3
 (1360#). PLEASE CORRECT.
  
 7) T30 AT JOINT 10 (UPLIFT 912#) EXCEEDS
 CAPACITY OF A1 (755#). PLEASE CORRECT.
  
 8) T32 (UPLIFTS 839# AND 1112#) EXCEED
 CAPACITY OF A1 (755#). PLEASE CORRECT.
  
 TO AVOID DELAYS, CHECK THE UPLIFT
 CAPACITIES OF THE SPECIFIED CONNECTORS
 TO ENSURE THAT THEY ARE CAPABLE OF
 RESISTING THE IMPOSED LOADS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202