Date |
Text |
2002-01-09 00:00:00 | TRUSSES DENIED |
| |
| 1) PROVIDE (2) SETS OF TRUSS DRAWINGS |
| AND LAYOUTS. THE LAYOUTS ARE REQUIRED TO |
| BE SIGNED, SEALED AND DATED BY THE TRUSS |
| ENGINEER. THE ENGINEER'S TITLE BLOCK IS |
| REQUIRED. INDICATE THE DESIGN CRITERIA |
| USED ON THE LAYOUT. ASCE7-95 (140 MPH |
| WINDLOAD) OR 97 SBC SECTION 1606 (110MPH |
| WINDLOAD). |
| |
| 2) THE LAYOUT MUST BE REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD FOR |
| THE STRUCTURE (JOHN AVERKAMP, INC.). |
| THIS IS TO BE INDICATED ON THE TRUSS |
| LAYOUT. |
| |
| 3) THE DESIGN CRITERIA INDICATED ON THE |
| TRUSS DRAWINGS IS INCORRECT. THE CORRECT |
| DESIGN CRITERIA IS ASCE7-95 (140 MPH |
| WINDLOAD) OR 1997 STANDARD BUILDING CODE |
| SECTION 1606 (110 MPH WINDLOAD). |
| |
| 4) THE TRUSS DRAWINGS ARE REQUIRED TO BE |
| DATED BY THE TRUSS ENGINEER INDICATING |
| THE DATE THEY WERE SEALED. |
| |
| 5) THE TRUSS LAYOUT AND THE ROOF FRAMING |
| PLAN (SHEET 6) HAVE SIGNIFICANT |
| DIFFERENCES. PLEASE SUBMIT A REVISED |
| ROOF FRAMING PLAN. |
| |
| 6) TRUSS T1 (UPLIFT 1891#) EXCEEDS THE |
| CAPACITY OF THE SPECIFIED CONNECTOR, A3 |
| (1360#). PLEASE CORRECT. |
| |
| 7) T30 AT JOINT 10 (UPLIFT 912#) EXCEEDS |
| CAPACITY OF A1 (755#). PLEASE CORRECT. |
| |
| 8) T32 (UPLIFTS 839# AND 1112#) EXCEED |
| CAPACITY OF A1 (755#). PLEASE CORRECT. |
| |
| TO AVOID DELAYS, CHECK THE UPLIFT |
| CAPACITIES OF THE SPECIFIED CONNECTORS |
| TO ENSURE THAT THEY ARE CAPABLE OF |
| RESISTING THE IMPOSED LOADS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |