2001-10-09 00:00:00 | ***************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE, PLANS ARE JUST NOW | | BEING SUBMITTED WITH AN ELECTRICAL | | RISER DIAGRAM/PANEL SCHEDULE AND LOAD | | CALCULATIONS. | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL AND COLD WATER | | PER 250-50. | | | | 5)NOTE: PLEASE NOTE THAT RISER SHOWS AN | | EQUIPMENT GROUNDING CONDUCTOR BEING | | INSTALLED BETWEEN METER AND FIRST MEANS | | OF DISCONNECT? PLEASE NOTE THAT THIS IS | | PARALLELING THE NEUTRAL. | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|