2001-10-09 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, PLANS ARE JUST NOW
 BEING SUBMITTED WITH AN ELECTRICAL
 RISER DIAGRAM/PANEL SCHEDULE AND LOAD
 CALCULATIONS.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 5)NOTE: PLEASE NOTE THAT RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METER AND FIRST MEANS
 OF DISCONNECT? PLEASE NOTE THAT THIS IS
 PARALLELING THE NEUTRAL.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372