Plan Review Notes For Permit 01080609 |
Permit Number |
01080609 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-23 00:00:00 | ***************** UNSAT *************** | | | | 1) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | PLEASE SEE MISSING LOCATIONS THROUGHOUT. | | | | 2) PLEASE NOTE MISSING OUTLET FOR A/C | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | MECHANICAL CODE. | | | | 3)NOTE: PLEASE NOTE THAT SMOKE DETECTORS | | ARE TO BE INSTALL A MIN OF 3` FROM | | BATHS/ PER NFPA-72 2-5.2.1.6 | | | | 4)NOTE: PLEASE NOTE MISSING OUTLET FOR | | GARAGE PER 210-52G AND GFI PER 210-8. | | | | 5)NOTE: PLEASE NOTE THAT NO RISER | | DIAGRAM WAS SUBMITTED FOR REVIEW???? | | PLEASE NOTE THAT NO LOAD CALCULATIONS | | WERE SUBMITTED. 215-5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELELCTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|