Plan Review Notes
Plan Review Notes For Permit 01080556
Permit Number 01080556
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-24 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT CUT SHEETS
 SHOWINGUL LISTINGS FOR EQUIPMNET.
  
 2)NOTE: PLEASE SUBMIT DIA GRAM SHOWING
 SYSTEM BEING HARDWIRED. PLEASE NOTE THAT
 THE CORDS ARE BEING SHOWN RUNNING
 THROUGH AREAS SUBJECT TO FIRE WALLS AND
 PHYSICAL DAMAGE
  
 3)NOTE: PLEASE SUBMIT INFOMATION ON SIZE
 OF PUMPS.
  
 4)NOTE: PLEASE SUBMIT A CONTRACT TO
 VERIFY VALUE. VALUE TO INCLUDE ALL
 LABORAND MATERIALS EVEN IF OWNER
 SUPPLIED.
 PER 104.7.5 OF LOCAL ADMINISTRATIVE
 CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372