2001-09-05 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE A0. WILL NEED TO PROVIDE |
| THE ELEVATION CERTIFICATE. |
| 2-SURVEY SHOW TWO STORY TOWNHOUSE FOR |
| LOT 123. REVISE AS REQUIRED. |
| 3-REVISE THE DESIGN CERTIFICATION FOR |
| BUILDING CODE COMPLIANCE FORM. |
| -THE MEAN ROOF HEIGHT IS INCORRECT. |
| MEAN ROOF HEIGHT IS TAKEN FROM THE |
| FINISH GRADE, NOT FROM THE FIN. FL, |
| TO THE AVERAGE POINT OF THE HIGHEST |
| ROOF. THEREFORE, MEAN ROOF HEIGHT IS |
| +/- 15'-6" SEE EXTERIOR ELEVATIONS. |
| -ALSO, REVISE THE BASIC VELOCITY |
| PRESSURE ACCORDINGLY. SEE TABLE |
| 1606.2A SBC 1997. |
| 4-ENERGY CALCULATIONS SHOW MULTIFAMILY |
| FOR 5 UNITS. THIS BUILDING HAS ONLY |
| THREE. REVISE AS REQUIRED. |
| -ALSO REVISE THE #OF BEDROOMS ACOORDING |
| TO THE OPTIONS SELECTED. |
| 5-PROVIDE ACTUAL DADE COUNTY PRODUCT |
| APPROVAL FOR STRUCTURAL WINDOW MULLION |
| 6-REVISE SHEET SH-1. GLASS BLOCK TO BE |
| USED SHALL HAVE 2 HOUR FIRE RATING AT |
| 2 HR WALL SEPARATION BET. TOWNHOUSES, |
| NOT 3/4 HR. |
| |
| |
| NOTES: |
| -DRAWINGS TO BE FILED UNDER PERMIT # |
| 01080506. |
| -THESE COMMENTS APPLY TO PERMIT #S: |
| 01080506, 01080498 AND 01080507. |