2001-08-13 00:00:00*******************PROVISO**************
  
  
 AHU 1 - NO ACCESS INDICATED ON PLAN.
 ACCESS FOR ATTIC INSTALLATION SHALL
 COMPLY WITH 1997 SMC 304.4.1 (ACCESS
 OPENING SHALL BE NO LESS THAN 22" X
 36").ALL AIR CONDITIONING/HEATING
 EQUIPMENT INSTALLED IN ATTIC SHALL HAVE
 AN ACCESSIBLE DISCONNECT SWITCH AND A
 110-120 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET.
  
 ALIGHT SHALL BE PROVIDED ON SERVICE
 SIDE OF EQUIPMENT CONTROLLED BY A
 SWITCH AT ATTIC OPENING.
  
 DRAIN PANS WITH OVERFLOW PROTECTION ALSO
 REQUIRED AS PER 1997 SMC 304.8.6.1.
  
  
  