Plan Review Notes
Plan Review Notes For Permit 01080403
Permit Number 01080403
Review Stop E
Sequence Number 4
Notes
Date Text
2002-01-30 00:00:00****************** UNSAT **************
  
 PLEASE NOTE THAT SOME ITEMS FROM PROVISO
 WERE NOT ADDRESSED FROM PREVIOUS REVIEW.
  
 1)NOTE: PLEASE NOTE WIRE SIZE SHOWN AT
 #3, IS ONLY RATED FOR 100AMPS. PLEASE
 NOTE PLANS SHOW 125A DISC AND PANEL?
  
 2)NOTE: PLEASE SHOW EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN DISC TO PANEL.
  
 3)NOTE: PLEASE SHOW LOAD CALCAULATIONS
 PER 220-3/220-10/220-11/220-13 AND
 ALL CONTINUOUS LOADS AT 125%.
  
 4)NOTE:PLEASE CLARFIY LOAD SHOWN FOR
 A/C. SHOWN AT 4500W? TYPICAL A/C HEAT
 IS 5KW/7KW ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372