Plan Review Notes For Permit 01080403 |
Permit Number |
01080403 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2002-01-30 00:00:00 | ****************** UNSAT ************** | | | | PLEASE NOTE THAT SOME ITEMS FROM PROVISO | | WERE NOT ADDRESSED FROM PREVIOUS REVIEW. | | | | 1)NOTE: PLEASE NOTE WIRE SIZE SHOWN AT | | #3, IS ONLY RATED FOR 100AMPS. PLEASE | | NOTE PLANS SHOW 125A DISC AND PANEL? | | | | 2)NOTE: PLEASE SHOW EQUIPMENT GROUNDING | | CONDUCTOR FROM MAIN DISC TO PANEL. | | | | 3)NOTE: PLEASE SHOW LOAD CALCAULATIONS | | PER 220-3/220-10/220-11/220-13 AND | | ALL CONTINUOUS LOADS AT 125%. | | | | 4)NOTE:PLEASE CLARFIY LOAD SHOWN FOR | | A/C. SHOWN AT 4500W? TYPICAL A/C HEAT | | IS 5KW/7KW ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|