Plan Review Notes
Plan Review Notes For Permit 01080403
Permit Number 01080403
Review Stop E
Sequence Number 3
Notes
Date Text
2002-01-10 00:00:00******** PROVISO /REVISION************
  
  
 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE REVISED. PLEASE SEE 220-3,
 220-10,220-11,220-13. LIGHTING=WATTS/PER
 SQ FT.TRACK LIGHTING PER 220-12B 150VA
 PER 2' OF TRACK.
 PLEASE NOTE ALL CONTINUOUS LOADS TO BE
 SHOWN AT 125%.(LIGHTING) 215-3/230-42
 OUTLETS PER 220-13 180VA PER OUTLET.
  
 2)NOTE: PLEASE NOTE THAT CONDUCTORS
 FEEDING PANEL 3A ARE ONLY RATED FOR
 100AMPS. PLEASE SEE 310-16 FOR CORRECT
 CONDUCTOR SIZING FOR 125A`S. IF 125A
 DISCONNECT OS FUSED DOWN? PLEASE SHOW.
  
 3)NOTE: PLEASE NOTE THAT NOTE ON PLAN
 SHOWS CIRCUITS FOR THE TENANT SPACE
 TO BE CIRCUITED TO ELECTRICAL ROOM?
 PLEASE NOTE ALL OTHER TENANT SPACES HAVE
 THERE OWN ELECTRICAL PANEL,PLEASE NOTE
 EACH TENANT MUST HAVE ACCESS TO THEIR
 OWN PANEL/CIRCUITS IN ORDER TO TURN
 OFF IF NEEDED/OR IF SOMETHING TRIPPED,
 THEY WOULD BE ABLE TO RESET. PLEASE
 ALSO NOTE THAT ELECTRICAL ROOMS MUST
 BE ACCESSIBLE TO QUALIFIED PERSONNEL
 ONLY? PLEASE NOTE THAT A NEW PANEL IN
 SPACE WOULD MOST LIKELY BE REQUIRED.
 A BLDG UNDER SINGLE MANGAMENT CAN MEET
 THE REQUIREMENT AS LONG AS A "QUALIFIED"
 PERSON IS AVAILABLE DURING BUSINESS HOUR
 -S. PLEASE NOTE THAT A "QUALIFIED PERSON
 IS SOMEONE THAT HOLDS AN ELECTRICAL
 LICENSE OF SOMEKIND(JOURNEYMAN) ETC.
 PLEASE CALL TO GO OVER THIS. PER NEC
 REGULATIONS.
  
 PLEASE SUBMIT THE ABOVE REVISION FOR
 REVIEW BEFORE ANY ROUGH INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. IF A MEETING IS NEEDED TO
 GO OVER ANYTHING, PLEASE DO NOT HESITATE
 IN CONTACTING ME.
  