2001-10-08 00:00:00********************DENIED**************
  
 PLEASE SHOW COMPLIANCE WITH THE 1997
 FLORIDA ENERGY CODE.
  
  
 THE SUPPLY OF HEATING AND COOLING TO
 EACH ZONE SHALL BE CONTROLLED BY
 INDIVIDUAL THERMOSTATIC CONTROLS FOR
 CONTROLLING THE TEMPERATURE WITHIN THE
 ZONE.
  
 SYSTEMS THAT SERVE ZONES WHICH CAN BE
 EXPECTED TO OPERATE NON-SIMULTANEOUSLY
 FOR MORE THAN 750 HOURS PER YEAR SHALL
 INCLUDE ISOLATION DEVISES AND CONTROLS
 TO SHUT OFF OR SET BACK THE SUPPLY OF
 HEATING AND COOLING TO EACH ZONES
 INDEPENDENTLY.ISOLATION IS NOT
 REQUIRED FOR ZONES EXPECTED TO BE
 INOPERATIVE ONLY WHEN ALL OTHER ZONES
 ARE INOPERATIVE.
  
 FOR BUILDINGS WHERE OCCUPANCY PATTERNS
 ARE NOT KNOWN AT THE TIME OF SYSTEM
 DESIGN, SUCH AS SHELL BUILDINGS,
 ISOLATION AREAS MAY BE PREDESIGNATED.
  
 THE EXISTING OFFICE SPACE (NO SUITE
 DESIGNATED) SHALL HAVE A RETURN AIR
 FROM THIS SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.