Plan Review Notes
Plan Review Notes For Permit 01080403
Permit Number 01080403
Review Stop M
Sequence Number 1
Notes
Date Text
2001-08-24 00:00:00*******************DENIED***************
  
  
 1.CFM DISTRIBUTION ON PLAN ADDS UP TO
 2200 CFM, WHEREAS A/C EQUIPMENT
 SCHEDULE INDICATES UNIT CFM = 1850.
 PLEASE CORRELATE SCHEDULE AND PLAN.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO SUPERVISORY
 SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION OR TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. NFPA 90A
 4-4.4.2 OR 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.