2001-08-21 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ALL EXITING
 AND EMERGENCY LIGHTING NEEDS TO BE
 SHOWN ON LAYOUT. PLEASE NOTE THAT SUITE
 301 EXISTINGSHOWS NEW WIRING? PLEASE
 SHOW EM LIGHTING AND EXIT LTS.
  
 2)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUITING NEEDS TO BE SHOWN ON PLANS
 INCLUDING LIGHTING.
  
 3)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN DISC AND PANEL.
 250-122
  
 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 NEW DISCONNECT ALSO. 110-9/215-5
  
 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 SERVICE? LOAD SHOWN AT 85AMPS. 11,120/
 240V.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT COMMENTS CAN
 BE GONE OVER ON THE PHONE OR IN PERSON.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372