2001-10-22 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT PERMIT AND PLAN
 -S WERE ORIG SUBMITTED FOR A 120/240
 SERVICE. NOW, IT IS BEING SUBMITTED FOR
 277/480. PLEASE NOTE THAT PER 553-79-6A
 FS/FAC 277/480 IS REQ`D TO BE SIGNED,
 DATED AND SEALED BY A P.E.
  
 2)NOTE: PLEASE ALSO NOTE THAT ALL FEEDER
 -S AND SUB FEEDERS MUST BE A RACEWAY PER
 215-12.LOCAL AMENDMENTS
  
 3)NOTE: PLEASE ALSO NOTETHAT GROUNDING
 CONDUCTORS ARE NOT PERMITTED TO BE
 ALUM. PER 310-2 LOCAL PALM BEACH COUNTY
 AND CITY-WIDE AMENDMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372