Plan Review Notes
Plan Review Notes For Permit 01080364
Permit Number 01080364
Review Stop P
Sequence Number 2
Notes
Date Text
2001-10-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) VARIANCE NOT APPROVED. SPC-97 NOT
 ADOPTED IN PALM BEACH COUNTY. PLEASE
 SUBMIT CALCULATIONS FOR MINIMUM FACILIT-
 IES PER SPC-94 TABLE 407.
  
 2) WATER HAMMER ARRESTORS TO BE PLACED
 NEAR SOURCE NOT AT TOP OF DROPS PER
 MANUFACTURES INSTALLATION INSTRUCTIONS
 AND WH-PDI 201.
  
 3) PAGE A.3 DOOR SHALL NOT OPEN INTO
 CLEAR FLOOR SPACE PER FACBC-9 SEC 4.22.2
 DOORS TO HDCP BATHROOMS SHALL OPEN OUT.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377