2001-10-13 00:00:00*******************DENIED***************
  
  
 1.AHU #2 INDICATES A FIRE DAMPER ON
 THE O.A. DUCT PENETRATING THE AHU
 CLOSET.IS THE CLOSET RATED?
  
 2.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 THE FOLLOWING COMMENTS FROM REVIEW DATED
 8-21-01 WERE NEVER ADDRESSED.
  
 1. CLARIFICATION OF CONDENSATE DRAINS.
  
 2. DUCT SMOKE DETECTORS TIED TO ALARM/
 STROBE.
  
 3. AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.