Plan Review Notes For Permit 01080364 |
Permit Number |
01080364 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-10-13 00:00:00 | *******************DENIED*************** | | | | | | 1.AHU #2 INDICATES A FIRE DAMPER ON | | THE O.A. DUCT PENETRATING THE AHU | | CLOSET.IS THE CLOSET RATED? | | | | 2.NO COMBUSTIBLES ABOVE THE CEILING | | IN THE RETURN AIR PLENUM. | | | | THE FOLLOWING COMMENTS FROM REVIEW DATED | | 8-21-01 WERE NEVER ADDRESSED. | | | | 1. CLARIFICATION OF CONDENSATE DRAINS. | | | | 2. DUCT SMOKE DETECTORS TIED TO ALARM/ | | STROBE. | | | | 3. AIR BALANCE SCHEDULE SHOWING | | COMPLIANCE WITH 1997 SMC 501.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | 8388. |
|