Plan Review Notes For Permit 01080364
Permit Number 01080364
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-23 00:00:00DENIED
  
 1) MORE FIXTURES REQUIRED. PLEASE SUBMIT
 CALCULATIONS FOR MINIMUM FIXTURES REQ-
 UIRED FOR WATER CLOSETS AND LAVS. PER
 SPC-94 TABLE 407.
  
 2) WATER HEATER TO BE READILY ACCESSABLE
 PER SPC-94 SEC. 501.7. PLEASE SHOW DE-
 TAILS.
  
 3) WATER HAMMER ARRESTORS TO BE INSTALL-
 ED PER MANUFACTURE'S INSTALLATION INSTR-
 UCTIONS AND PDI WH 201.
  
 4) PLEASE SUBMIT CALCULATIONS FOR ROOF
 DOWN SPOUTS AND OVERFLOW SCUPPERS USING
 CHAPTER 11 SPC-94 SECTIONS 1108 AND 1109
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377