Plan Review Notes For Permit 01080364 |
Permit Number |
01080364 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-23 00:00:00 | DENIED | | | | 1) MORE FIXTURES REQUIRED. PLEASE SUBMIT | | CALCULATIONS FOR MINIMUM FIXTURES REQ- | | UIRED FOR WATER CLOSETS AND LAVS. PER | | SPC-94 TABLE 407. | | | | 2) WATER HEATER TO BE READILY ACCESSABLE | | PER SPC-94 SEC. 501.7. PLEASE SHOW DE- | | TAILS. | | | | 3) WATER HAMMER ARRESTORS TO BE INSTALL- | | ED PER MANUFACTURE'S INSTALLATION INSTR- | | UCTIONS AND PDI WH 201. | | | | 4) PLEASE SUBMIT CALCULATIONS FOR ROOF | | DOWN SPOUTS AND OVERFLOW SCUPPERS USING | | CHAPTER 11 SPC-94 SECTIONS 1108 AND 1109 | | | | REVIEW BY KEN STEVENS | | (561) 569-8096 EXT. 8377 |
|