Plan Review Notes For Permit 01080364 |
Permit Number |
01080364 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-21 00:00:00 | *******************DENIED*************** | | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62.89 | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | COMPLIANCE WITH 1997 SMC 501.2 | | 3. BATHROOM EXHAUST FANS NEED MORE | | INFORMATION, INCLUDING CFM. | | 4. NO CFM SHOWN AT A/C DROP IN WOMEN'S | | BATHROOM | | 5. DUCT SMOKE DETECTORS WITH | | NOTIFICATION TO BUILDING FIRE ALARM OR | | HORN AND STROBE IF NO BLDG FIRE ALARM | | SYSTEM REQUIRED FOR BOTH AHUS. | | 6. PLEASE CLARIFY THE CONDENSATE DRAINS. | | PRIMARY IS NOT SHOWN ON PLAN AND | | EMERGENCY DRAIN NEEDS TO TERMINATE IN | | CONSPICUOUS LOCATION. | | IF CONDENSATE FOR AHU ZONE 2 TERMINATES | | ON WEST SIDE OF BUILDING AS SHOWN,IS | | THERE A PERVIOUS AREA ON THIS PROPERTY | | FOR THE DRAIN TO RUN TO? | | CONDENSATE SHALL EITHER TERMINATE IN A | | STORM SEWER OR APPROVED DRYWELL. | | 7. CONDENSING UNITS ARE TO BE ON SOLID | | CONCRETE PADS MINIMUM 3" ABOVE | | ADJOINING GRADE. |
|