Plan Review Notes
Plan Review Notes For Permit 01080364
Permit Number 01080364
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-28 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 IS SHOWING ALL 2-POLE BRKRS ON LEFT AND
 RIGHT OF PANEL ON THE SAME PHASE. PLEASE
 CORRECT. ALL 2POLE BRKRS SHOULD LINE UP
 ON SAME SIZE FOR 220V
  
 2)NOTE: PLEASE NOTE LOAD FOR WATER HEAT-
 -ER NEEDS TO CORRELATE W/ LOAD SHOWN ON
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 IS MISSING RISER SIZE, WIRE SIZE FROM
 RISER TO METER TO MAIN DISCONNECT.
  
 4)NOTE: PLEASE ALSO NOTE THAT PLANS SHOW
 MAIN DISCONNECT AND A MCB PANEL. PLEASE
 NOTE PANEL MAY HAVE MAIN ALSO BUT IS NOT
 REQUIRED W/ MAIN DISCONNECT OUTSIDE.
  
 5)NOTE: PLEASE NOTE ALL CONTINOUS LOADS
 TO BE SHOWN AT 125%. (LIGHTING) ETC.
 PER 230-42/215-3
  
 6)NOTE: PLEASE NOTE LOAD SHOWN FOR WATER
 HEATER AT 1500 WATTS AND 20KW ?? WHICH
 ONE? PLEASE ALSO NOTE THAT IF 1500WATTS
 THEM THE MAX OCP IS AT 150%. YOU SHOW
 A 2-P-30. PLEASE CORRECT
  
 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SHOWS CWP, NOT BLDG STEEL.
  
 8)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW ALL BRANCH CIRCUIT #`S ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES.215-5
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING IS SHOWN FOR
 PANEL, BUT NOT FOR MAIN. PLEASE SUBMIT
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372