Plan Review Notes For Permit 01080364 |
Permit Number |
01080364 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-09-14 00:00:00 | | | BUILDING COMMENTS | | ----------------- | | | | 1] | | SHOWER SHALL COMPY WITH ACCESSIBILITY | | REQUIREMENTS, SEE 4.21 FAC. | | 2] | | FOOTING DETAILS SHOW 3 BARS, AND THE | | NOTE ONLY CALLS FOR 2? | | BOTTOM OF FOOTINGS SHALL BE MINIMUM 12" | | BELOW GRADE. | | 3] | | THE WEST ELEVATION WALL SHALL NOT HAVE | | ANY OPENINGS PER TABLE 600 SBC, 0-3FT. | | ALSO SEE 705 SBC FOR PROTECTED OPENINGS | | WHEN IF EXTERIOR WALLS ARE LESS THAN | | 15FT. FROM P/L. | | 4] | | CASEMENT WINDOWS SHALL NOT OPEN OVER | | PUBLIC PROPERTY AT NORTH ELEVATION. | | 5] | | PROVIDE COMPLETED FLA. ENERGY EFF. | | REPOTS. | | 6] | | SUBMIT PRODUCT TESTING FOR ALL EXTERIOR | | WINDOWS AND DOORS, WIND COMPLIANCE AND | | IMPACT RESISTANCE FOR GLAZING. SUBMIT | | TEST REPORT FOR ROOF COVERS. | | 7] | | SHOW ACCESSIBLE ROUTE FROM PARKING | | SPACE TO THE MAIN ENTRANCE, GATES SHALL | | BE ACCESSIBLE TYPE. | | 8] | | P.B.C COUNTY IMPACT FEES AND CITY RADON | | FEES ARE DUE. | | | | | | REVIEWED BY: | | LUIS MARTINEZ | | 659-8096 | | #8456 |
|