Plan Review Notes For Permit 01080287 |
Permit Number |
01080287 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-22 00:00:00 | DENIED | | REFERENCES SPC-94/FACBC-97 | | | | 1) DRINKING FOUNTAIN REQUIRED PER SPC-97 | | TABLE 407. MUST COMPLY WITH FACBC-97 | | SECT. 4.15 | | | | 2) PER FACBC-97 SEC. 4.17.3 EXCEPTION | | FOR NEW CONSTRUCTION #2 ACCESSABLE W/C | | SHALL BE LOCATED IN THE CORNER, DIAGONAL | | TO THE DOOR. | | | | 3) W/C'S TO COMPLY WITH FACBC-97 SEC. | | 4.16 | | | | 4) LAVS. TO COMPLY WITH FACBC-97 SEC. | | 4.19 | | | | 5) FITTING ROOM BENCHES TO COMPLY WITH | | FACBC-97 4.35.4 | | | | 6) SBC-97 1204.2 WALLS IN RESTROOMS TO | | BE LINED WITH NONABSORBENT MATERIAL. | | PLEASE SHOW DETAILS. | | | | 7) PAGE P-2 "G" PIPE AND MATERIALS, AND | | "J" FIXTURE STOP AND AIR CHAMBERS, AIR | | CHAMBERS TO COMPLY WITH SPC-94 607.8.2 | | AND 607.8.3. | | | | 8) PAGE P-2 - PLUMBING GENERAL NOTES. | | CONNECTION TO LANDLORDS PLUMBING SYSTEM, | | #13 WATER HAMMER ARRESTORS TO BE INSTALL | | ED IN COMPLIANCE WITH MANUFACTURES IN- | | STALLATION INSTRUCTIONS. | | | | 9) PAGE P-2 - HANGER ROD SPACING. HANGER | | SPACING TO BE ACCORDING TO SPC-94 SEC. | | 310.3 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|