1 |
|
Notes |
Date |
Text |
2001-08-08 00:00:00 | 1) BUILDING CODE ANALYSIS BOX INDICATES | | 250 FEET FOR TRAVEL DISTANCE. THE | | PREVAILING FIRE CODE ALLOWS 150 FEET | | MAXIMUM IN SPRINKLER PROTECTED | | MERCANTILE OCCUPANCIES. | | 2) GENERAL NOTES INDICATES BUCKS COUNTY, | | STATE OF PENNSYLVANIA. PROJECT IS | | LOCATED IN PALM BEACH COUNTY, STATE OF | | FLORIDA. | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE ALARM SYSTEM REMODEL. | | 4) EXITING PERMITTED THRU STOCKROOM IF | | THE FOLLOWING CONDITIONS EXIST: DOOR | | TO STOCKROOM IS NOT LOCKED, AN AISLE OF | | AT LEAST 44" WIDE IS PROVIDED AND | | MAINTAINED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|