Plan Review Notes
Plan Review Notes For Permit 01080287
Permit Number 01080287
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-08 00:00:001) BUILDING CODE ANALYSIS BOX INDICATES
 250 FEET FOR TRAVEL DISTANCE. THE
 PREVAILING FIRE CODE ALLOWS 150 FEET
 MAXIMUM IN SPRINKLER PROTECTED
 MERCANTILE OCCUPANCIES.
 2) GENERAL NOTES INDICATES BUCKS COUNTY,
 STATE OF PENNSYLVANIA. PROJECT IS
 LOCATED IN PALM BEACH COUNTY, STATE OF
 FLORIDA.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM REMODEL.
 4) EXITING PERMITTED THRU STOCKROOM IF
 THE FOLLOWING CONDITIONS EXIST: DOOR
 TO STOCKROOM IS NOT LOCKED, AN AISLE OF
 AT LEAST 44" WIDE IS PROVIDED AND
 MAINTAINED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910