2001-08-21 00:00:00 | **************** UNSAT *************** |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| IT IS SHOWN ON PANELS AS?? PLEASE NOTE |
| RATINGS ARE REQ`D FOR ALL.215-5 |
| |
| 2)NOTE: PLEASE NOTE THAT UNDER CITY OF |
| WEST PALM BEACH LOCAL AMENDMENTS, OUTLET |
| SPACING AT EVERY 20' OF UNENCUMBERED |
| WALL SPACE INCLUDING STORAGE/STOCK AREA. |
| 210-50 |
| 3)NOTE: PLEASE SUBMIT CLARIFICATION ON |
| GROUNDING OF TRANSFORMER PER 250-30. |
| |
| 4)NOTE: PLEASE ALSO NOTE PER LOCAL |
| AMENDMENTS, COLOR CODING OF 277/480V |
| IS BROWN/PURPLE/YELLOW PER ART215 OF |
| LOCAL AMEND. |
| |
| 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS] |
| LOADS NEED TO BE SHOWN PER 215-3 AND |
| 230-42. PLEASE ALSO NOTE THAT LOAD |
| CALCUALTIONS NEED TO BE COMPLETED AND |
| SHOWN. PER 215-5 |
| |
| 6)NOTE: PLEASE SEE A-0, PLEASE NOTE |
| THAT PLANS REFERENCE THE 1996 NEC. |
| PLEASE NOTE THAT WE ARE UNDER THE 99 NEC |
| PLEASE ALSO NOTE THAT GENERAL NOTES ON |
| SAME PAGE MENTION THAT ALL WORK TO |
| COMPLY WITH "BUCKS COUNTY" PA. |
| PLEASE CORRECT. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |