2001-08-14 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080287
 700 S ROSEMARY #106
 "PLAN REVIEW"
 SBC= STANDARD BUILDING CODE (1997)
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
  
 1)- SHEET A-1 BLOCKING ALL WOOD USED IN
 WALLS ARE TO BE NON-COMBUSTIBLE OR FRT
 FIRE RETARDANT TREATED SBC 609.22.1
 SHEET A-6 HEADERS / JAMBS FRT WOOD.
 2)- SHEET A-2 DETAIL #1 SPACING OF METAL
 HIGH HAT NOT GIVEN, NOR IS THE SPACING
 OF THE C-CHANNEL. SPACING OF THE HANGER
 WIRE OR GAUGE. TYPE OF FASTENER TO DECK
 ABOVE?
  
 3)- SHEET A-2 DETAIL # 1 & 3 DO NOT GIVE
 THE ANCHORING OF THE TOP PLATE OR THE
 SPACING OF THE STUDS.
  
 4)_ SHEET A-6 SBC 1204.2 REQUIRES A NON-
 ABSORBANT MATERIAL ON FLOORS AND WALLS
 TO A HEIGTH OF 4'-0" IN PUBLIC RESTROOMS
  
 5)- SBC 1001.1.2 SHOW MEANS OF EGRESS
 THROUGH OUT THE TENANT SPACE INDICATE
 THE 44" ACCESS (MINIMUM). STORAGE AREAS
 THOUGH NOT PROHIBITED AS A COMPONENT OF
 A MEANSOF EGRESS, REQUIRE SPECIAL
 CONSIDERATION. IT IS CRITICAL THAT THE
 REQUIRED MEANS OF EGRESS BE DESIGNATED &
 MAINTAINED TO INSURE THAT OBSTRUCTIONS
 ARE ELIMINATED. SPECIAL MARKINGS OR RAIL
 INGS OR SCREENS MAY BE USED TO SEPERATE
 THE DESIGNATED MEANS OF EGRESS FROM THE
 STORAGE USE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412