Plan Review Notes For Permit 01080245 |
Permit Number |
01080245 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-14 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT AN ELECTRIC | | HEATER IS BEING ADDED AND NO LOAD | | CALCULATIONS WERE SUBMITTED. PLEASE | | INCLUDE ALL NEW LOADS AND SHOW SIZE OF | | EXSITING SERVICE. | | | | 2)NOTE: PLEASE NOTE THAT ELECTRICAL | | WIRING DIAGRAM DOES NOT INCLUDE HEATER, | | WIRE SIZES, CONDUIT SIZE???? | | PLEASE SHOW AND ALL CHANGES ON SIGNED | | AND SEALED DRAWINGS MUST BE DONE BY THE | | ENGINEER OF RECORD. 471.025 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|