Date Text
2001-08-02 00:00:00*******************DENIED***************
  
  
 EF-1 ON ROOF - ROOF SLOPE IS INDICATED
 AS HAVING A SLOPE GREATER THAN 4:12
 SHALL HAVE A LEVEL WORKING PLATFORM NOT
 LESS THAN 30" AND COMPLY WITH 1997 SMC
 304.6.2.
  
 EF-1 SHALL COMPLY WITH 1997 SMC 506.1,
 SHALL BE LOCATED 10' FROM ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, OR AIR INTAKE.
  
 PLEASE CLARIFY SF-1, AS TO LOCATION OF
 DUCT WORK FROM FAN TO CEILING DIFFUSER.
 PLAN 2 OF 2 LOOKS AS IF FAN HAS A CURB
 BUT THERE IS NOTHING INDICATING WHERE
 THE PENETRATION IS AT. IS DUCT UNDER
 ROOF OR ON TOP?
  
 PLEASE SUBMIT MANUFACTURER DATA ON 3M
 FIREWRAP.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.