Plan Review Notes
Plan Review Notes For Permit 01080067
Permit Number 01080067
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-08 00:00:00DENIED..
  
 1) GAS PERMIT APPLICATION REQUIREMENT
 SHEET #4. SHOW TYPE OF MATERIAL. BTU
 VALUES ARE DIFFERENT FROM NUMBERS BY
 UNITS (FIXTURES), TO NUMBERS AT LIST
 WHERE THEY WERE ADDED. PLEASE CLEARIFY.
  
 2) INDICATE DELIVERY PRESSURE.
  
 3) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT.
  
 4) SHOW LOCATION OF SECOND STAGE REGU-
 LATOR IF TWO POUND SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved